Projector / Display (PJLink)| This
function block controls and monitors projectors and displays via
PJLink. PJLink is a cross-vendor standard of the JBMIA (Japan
Business Machine and Information System Industries Association) for
operation over the network. The block switches the device, selects
the input, mutes picture and sound and reports the state, faults and
operating hours. Create one block per device. The controller polls the device cyclically and disconnects immediately afterwards, as the standard requires. Settings on the device:
Warm-up and cool-down: A command stays pending until the device can accept it, for at most 5 minutes. If it still cannot be executed after that, output ER shows error code 4. If the device is switched off during warm-up, the command follows after the warm-up; switching on during cool-down follows after the cool-down. Input, picture and sound wait until the device is on, so "on" and an input can be set at the same time. While something is in progress, the block polls every 5 seconds. After the controller starts, the pending value of an input does not trigger a command, so a restart never switches the device. This also applies to changes in the first 30 seconds after the start and to responses to read requests. Changes made on the device with the remote control are not reverted, the outputs then show the actual state. Notes:
|
Inputs |
||
| FG |
Enable |
Optional. Non-zero enables. At 0 no connections are opened and no commands are sent, pending commands expire, ST and PW go to 0. Changes at the other inputs while disabled are not made up for. Not connected: the block counts as enabled. |
| EA |
On/Off |
Optional. Every change of value is evaluated: non-zero switches on, 0 switches to standby. Not connected: the block only monitors the device. |
| QU |
Select input |
Optional. Every change of value is evaluated: the value is the number of the input (see above), 0 does nothing. Not connected: no switching. |
| BA |
Picture off |
Optional. Every change of value is evaluated: non-zero mutes the picture, 0 restores it. If the device has no separate muting, the block switches picture and sound together. Not connected: no picture muting. |
| TA |
Sound off |
Optional. Like BA, but for the sound. Not connected: no sound muting. |
| FZ |
Freeze |
Optional. Class 2 only. Every change of value is evaluated: non-zero freezes the picture, 0 cancels it. On devices without this function, ER shows error code 3. Not connected: no freeze. |
| V+ |
Volume up |
Optional. Class 2 only. The change from 0 to non-zero is evaluated: one step louder. In standby the command expires. Not connected: no adjustment. |
| V- |
Volume down |
Optional. Like V+, but one step quieter. Not connected: no adjustment. |
Outputs |
||
| ST |
Connection |
1 = device responds. 0 only after three failed connections in a row, or immediately if the login is rejected. Short gaps right after switching are normal. |
| ER |
Error code |
0 = OK, 1 = no connection, 2 = login rejected (password or method), 3 = command rejected (e.g. input does not exist), 4 = command not possible within the time limit, 5 = device reports an error, 6 = device does not respond according to PJLink. Codes 3 to 5 from a command remain for 60 seconds. |
| EM |
On feedback |
1 = switched on or warm-up, 0 = standby, cool-down or no connection. |
| PW |
Operating state |
0 = standby, 1 = on, 2 = cool-down, 3 = warm-up. 0 if there is no connection, observe ST. |
| QA |
Active input |
Number of the active input, as with QU. Only updated when switched on. |
| BM |
Picture off feedback |
1 = picture muted. Some devices cancel muting by themselves when the input or the signal changes, which this output then also shows. |
| TM |
Sound off feedback |
1 = sound muted. |
| FM |
Freeze feedback |
1 = picture frozen. Class 2 only, otherwise 0. |
| SG |
Collective fault |
Highest value of the six faults: 0 = none, 1 = warning, 2 = error. |
| SL |
Fan fault |
0 = none, 1 = warning, 2 = error. 0 can also mean that the device does not have this monitoring. This applies to all faults. |
| SP |
Lamp fault |
Like SL. |
| TE |
Temperature fault |
Like SL. |
| SD |
Cover fault |
Like SL. Cover open. |
| SF |
Filter fault |
Like SL. |
| SO |
Other fault |
Like SL. |
| LH |
Lamp hours |
Operating hours of the lamp, with several lamps the highest value. 0 if the device has no lamp or does not count. |
| FH |
Filter hours |
Operating hours of the filter. Class 2 only, otherwise 0. |
| AU |
Input resolution |
Text, e.g. 1920x1080. Empty without a signal and in standby. Class 2 only. |
| NM |
Name |
Name set on the device (text). |
| HE |
Manufacturer |
Text. |
| MO |
Model |
Text. On the KNX bus, texts are cut off after 14 characters. |
Parameters |
||
| IP address / host name |
Address of the device in the network. IPv4 only. | |
| Port |
TCP port of the device (default 4352). | |
| Login |
Method if the device requires a login. MD5 (default) is the method of all PJLink devices. SHA-256 only exists from PJLink specification 2.10 of 2024. On devices without SHA-256, ER reports error code 2. | |
| Password |
PJLink password of the device, at most 32 letters and digits. Empty if the device does not require a login. | |
| Polling interval |
Interval between polls in seconds (5 to 600, default 10). With pending commands and during warm-up and cool-down, the block polls every 5 seconds. | |
| Timeout |
Time to wait per response in seconds (default 5). In standby, some devices respond more slowly. | |
| Debug |
Additional diagnostic output in the error log. The password is not output. | |
Manufacturers |
||
| The block follows the PJLink standard and is not tailored to individual manufacturers. The following overview is based on information from the manufacturers and the JBMIA, it is not a test by uni-PRO. The individual model is what counts, not every device of a manufacturer supports PJLink. This can change with new firmware. As of October 2026. The Check device button is suitable for checking, as is the product list of the JBMIA, which does not contain all devices, however. | ||
| Epson |
Class 2 according to the JBMIA list and the Epson documentation. On individual models, picture and sound can only be muted together. | |
| Sharp / NEC |
Class 1 and 2 according to the JBMIA list. The network is off by default on the PA, PX and PH series. | |
| Optoma |
Class 2 according to the JBMIA list. | |
| Fujifilm |
Class 2 according to the JBMIA list and the manufacturer's command list. Commands are only accepted about 60 seconds after switching on. | |
| Panasonic |
According to the network guide Class 1 at least on the PT-CW230 series. Check the manual of the model. | |
| Sony |
Depends on the model. The Help Guide of the VPL-CWZ10 mentions PJLink, the one of the VPL-GTZ380 does not. | |
| BenQ |
Depends on the model. According to BenQ, some models need an administrator password set in the browser beforehand. | |
| Barco |
According to the manual specification 2.00 on the series concerned. The function is off by default. | |
| JVC |
Class 1 on the LX-WX50 according to the manual. | |
| Casio, Ricoh |
Members of the PJLink subcommittee of the JBMIA. Check the model in the manual. | |
| Named by third parties |
Canon, Hitachi/Maxell, Christie, InFocus and Mitsubishi are named as PJLink-capable by providers of other control software. We had no information from the manufacturers, so this must be checked on the model. | |