X-Sense detector| The function block connects a smoke, CO, heat or combination detector from X-Sense that is paired with the SBS50 base station. The base station sends the state of its detectors to the controller via MQTT, without going through a cloud. One block is created for each detector. The connection is read-only: the block reports alarm and state, but cannot trigger or silence the detectors. Important: The block is for overview purposes only. Its messages may fail to arrive, arrive late or be wrong, for example if the base station has no Wi-Fi connection or no power, has lost its connection to the controller or cannot reach a detector. The block must therefore not be used for safety-related functions and does not replace a fire alarm system. The detectors warn over their own radio link, independently of the controller. The test button on the detector does not trigger a message on the block, so the alarm outputs cannot be tested with it. |
Setup |
||
|
||
Outputs |
||
| AL | Alarm | 1 while the detector reports smoke, CO or heat. Collective output of RA, CO and HI. |
| RA | Smoke alarm | 1 while the detector reports smoke. |
| CO | CO alarm | 1 while the detector reports carbon monoxide. Stays 0 on detectors without a CO sensor. |
| HI | Heat alarm | 1 while the detector reports heat. Stays 0 on detectors without a heat sensor. |
| ST | Fault | 1 while the detector reports a fault in one of its sensors. |
| BA | Battery low | 1 while the detector reports a low battery. |
| LE | End of life | 1 as soon as the detector reports the end of its service life. The detector must then be replaced. |
| ON | Online | 1 while the base station reports the detector as reachable. Also becomes 0 on a timeout. |
| TO | Timeout | 1 if no message for this detector arrived within the monitoring time. The alarm outputs keep their last value, because missing messages are not an all-clear. The next message sets the output to 0. |
Parameters |
||
| ID | ID of the detector as it appears in the MQTT topic, for example SBS50XXXXXXXX_0000000D. The ID is case-sensitive. | |
| Monitoring time | Time in seconds after which the TO output is set if no message arrives. The default is 900 seconds, which corresponds to three send cycles of the base station. 0 disables monitoring. | |
| After the controller starts, all outputs are 0 until the first message from the detector has arrived. This can take up to five minutes. If no messages arrive after that either, switch the MQTT connection in the X-Sense app off and on again. The base station does not send X-Sense water detectors and thermo-hygrometers via MQTT, so they cannot be connected with this block. |
See also MQTT devices - General.
See also general parameters of all
function blocks.