Block Code switch KNXThe code switch KNX turns an ordinary KNX push button into a code keypad, for instance at the entrance or at the garage: each rocker stands for a digit. For every button a function of its own with a code of its own can be stored, for example open the door or arm the alarm system. The control element shows whether the code switch is enabled, offers the same code entry on the screen and is used to change the codes.
At the KNX push button a short press enters a digit, a long press selects the function of this button; its LED then lights up. A correct code makes the LED flash for a few seconds, a wrong one all LEDs. If the code is not completed within 10 seconds, it counts as wrong.
If Function selection is set to None at the function block, there is no function to select: the controller checks all codes, each triggers its own output. Codes can then only be assigned with the master code. After the master code, Which code? Select button appears; the green dots show which codes are already assigned. Then Password new and Password new repeat follow. A code that is already assigned is rejected with Code already assigned.
If a lock after wrong attempts is set at the function block, Too many wrong attempts, input locked appears after too many wrong codes. If the push button is locked, the tile shows Locked.
As long as the settings have not yet been loaded from the controller, Please wait is shown instead of the digit buttons.
Behind the clock there are switching times that enable or lock the code switch – for example enabled during the day and locked at night. Everything else about switching times is described under Presence.
Behind the house you set whether the code switch is enabled (Active) or locked (Inactive) when the presence changes. A tap on a symbol selects whether switching takes place for this state at all. Switching times and presence only act when an enable is set up.
A one-time code is an additional code generated at random, for instance for craftsmen or guests. It applies to every function.
Time and time factor act at once, Ok closes the dialog.
This section is meant for the installer of the system.
The control element is linked to the function block Block KNX Code switch: first create the function block and its addresses, then right click on the control element and select the function block. In the same menu Take comment takes over the name of the function block as text. See also Presence.
Display |
|
| View | Block or Basic Screen. The third choice List (deprecated) comes from older projects and should no longer be used. |
| Text | Caption of the tile, default Code KNX. Its size scales with the element, a line break is inserted with \n, two lines at most. |
All addresses sit at the function block and are taken over when linking.
See also General properties of all control elements.